Transformer Calculations Question & Answers

November 9, 2026 By Wat Electrical

Transformers sit quietly at almost every point of the power system, from the generating station to the pole-mounted unit outside your home. They have no moving parts and rarely draw attention, yet nearly every unit of electrical energy you use has passed through several of them. A single transformer also holds a set of design trade-offs in its losses, its voltage drop under load, and the way it shares current with its neighbours.

That is why transformer calculations are a core skill for electrical engineering students and for anyone preparing for GATE, ESE, or utility recruitment exams. The theory is short. The difficulty is in applying it under time pressure: choosing the right formula, referring values to the correct side, and keeping track of power factor and load fraction. Reading the equations once does not build that skill. Solving varied problems does.

This article is a practice set of 100 multiple-choice questions built around four themes:

Losses: what iron and copper losses depend on, and how the open-circuit and short-circuit tests reveal them.

Efficiency: full-load, part-load, maximum, and all-day efficiency.

Voltage regulation: the effect of load power factor, per-unit values, and short-circuit current.

Parallel operation: load sharing, circulating currents, and which transformers can be connected.

A short opening set covers basic ratios and EMF, and a closing set covers mixed topics such as short-circuit level, per-unit conversion, and autotransformers.

How to use this bank

  • Attempt each question before reading the hint.
  • Each question has four options, a hint (the idea or formula to use), and the answer with a short working.
  • Unless stated otherwise, the transformers are single-phase, the frequency is 50 Hz, and the load is at rated voltage.
  • Voltage regulation is defined here relative to the no-load secondary voltage V20. This is the convention behind the approximate formula used in Section D. Some texts divide by the loaded voltage V2 instead, which gives slightly larger values (see Q54).
  • Per-unit conversions between kVA bases assume an unchanged voltage base unless stated.
  • Assume the paralleled transformers have the same X/R ratio, so their load currents are in phase and add arithmetically.

Key Formulas

Topic

Formula


EMF equation

E = 4.44 f Φm N
Turns ratio

K = N2/N1 = V2/V1 = I1/I2

Referred resistance (to secondary)

R02 = R2 + K² R1
Referred reactance (to secondary) X02 = X2 + K² X1
Iron loss

Pi = Ph + Pe, with Ph ∝ f B^1.6 and Pe ∝ f² B² t²

Copper loss at load fraction x

Pcu = x² × Pcu(fl)
Efficiency

η = x S cosφ / (x S cosφ + Pi + x² Pcu(fl))

Load for maximum efficiency

x = √(Pi / Pcu(fl))

Voltage regulation (defined on no-load voltage)

%VR = (V20 − V2)/V20 × 100

Voltage regulation (alternative, on loaded voltage)

%VR = (V20 − V2)/V2 × 100

Voltage regulation (approx.)

ε = ε_r cosφ ± ε_x sinφ (+ lagging, − leading)

Max regulation

ε = ε_z, at cosφ = ε_r/ε_z (lagging)

Zero regulation (leading)

tanφ = ε_r/ε_x

Load sharing in parallel

Sa : Sb = (Sa,rated / Za%) : (Sb,rated / Zb%)

Circulating current

Ic = ΔE / (Z1 + Z2)
Per-unit base change

Z_pu,new = Z_pu,old × (S_base,new / S_base,old) × (V_base,old / V_base,new)²

Q1). A single-phase transformer is rated 2200/220 V. If the primary has 1000 turns, the number of secondary turns is:

Hint
Q2). The peak flux in a core is 0.02 Wb and the winding has 200 turns at 50 Hz. The induced RMS EMF is approximately:

Hint
Q3). A 50 kVA, 2400/240 V single-phase transformer has a rated primary current of:

Hint
Q4). For the same transformer (50 kVA, 2400/240 V), the rated secondary current is:

Hint
Q5). A 3-phase, delta/star transformer is rated 11 kV/400 V (line values). The per-phase turns ratio N1/N2 is about:

Hint
Q6). An ideal transformer is rated 4400/220 V and the secondary supplies 100 A. The primary current is:

Hint
Q7). A 10 Ω load is connected across the secondary of an ideal 20:1 step-down transformer (N1:N2 = 20:1). The load as seen from the primary is:

Hint
Q8). The HV line current of a 3-phase, 100 kVA, 11 kV/400 V transformer is:

Hint
Q9). A transformer is operated at the same voltage but the frequency falls from 50 Hz to 40 Hz. The core flux:

Hint
Q10). A transformer has R1 = 2 Ω, R2 = 0.02 Ω and K = N2/N1 = 0.1. The equivalent resistance referred to the secondary is:

Hint
Q11). The iron loss of a transformer remains practically constant when:

Hint
Q12). The full-load copper loss of a transformer is 2000 W. At half load, the copper loss is:

Hint
Q13). The thickness of the core laminations is halved. The eddy current loss becomes:

Hint
Q14). The hysteresis loss at 50 Hz is 400 W. At 60 Hz with the same maximum flux density it is:

Hint
Q15). A transformer has an iron loss of 1000 W at 50 Hz (hysteresis 600 W, eddy 400 W). At 60 Hz with the same flux density, the iron loss is:

Hint
Q16). If the supply voltage rises by 10% at constant frequency, the iron loss rises by about:

Hint
Q17). The open-circuit (no-load) test on a transformer is used to find:

Hint
Q18). The short-circuit test is done at a reduced voltage because:

Hint
Q19). The no-load power factor is:

Hint
Q20)The magnetising current Im is about:

Hint
Q21). The core-loss resistance R0 (LV side) is:

Hint
Q22). The equivalent impedance Z01 referred to the HV side is:

Hint
Q23). The equivalent resistance R01 is:

Hint
Q24). The equivalent reactance X01 is:

Hint
Q25). A transformer has a full-load copper loss of 1200 W. At 80% load, the copper loss is:

Hint

Transformer Calculations MCQs for Exams

Q26). A transformer has an iron loss of 800 W and a full-load copper loss of 1600 W. The load fraction at which copper loss equals iron loss is:

Hint
Q27). Cold-rolled grain-oriented (CRGO) silicon steel is used for transformer cores mainly to reduce:

Hint
Q28). Stray load loss in a transformer is caused mainly by:

Hint
Q29). The full-load efficiency at 0.8 power factor lagging is:

Hint
Q30). The efficiency at half load, 0.8 pf, is:

Hint
Q31). The load (as a fraction of full load) at maximum efficiency is:

Hint
Q32). The kVA load at maximum efficiency is:

Hint
Q33). The maximum efficiency at 0.8 pf is about:

Hint
Q34). For a given power factor, the efficiency of a transformer is maximum when:

Hint
Q35). At a given load current, the efficiency of a transformer is highest at:

Hint
Q36). The full-load efficiency is:

Hint
Q37). The load at maximum efficiency is:

Hint
Q38). The maximum efficiency is:

Hint
Q39). All-day (energy) efficiency is defined as:

Hint
Q40). A 10 kVA distribution transformer has a core loss of 100 W and a full-load copper loss of 150 W. It runs 8 h at full load, unity pf, and 16 h at no load. The all-day efficiency is:

Hint
Q41). Distribution transformers are designed with a low iron loss relative to copper loss because:

Hint
Q42). A transformer delivers 49 kW and has an efficiency of 98%. Its total losses are:

Hint
Q43). A 20 kVA transformer has Pi = 300 W and Pcu(fl) = 400 W. At 75% load and unity pf, the efficiency is:

Hint
Q44). A 100 kVA transformer has Pi = 0.8 kW and Pcu(fl) = 1.2 kW. At 25% load and 0.9 pf, the efficiency is:

Hint
Q45). A transformer has maximum efficiency at 60% of full load and an iron loss of 1.2 kW. Its full-load copper loss is:

Hint
Q46). A transformer has a full-load copper loss of 2 kW and reaches maximum efficiency at 50% of full load. Its iron loss is:

Hint
Q47). The efficiency at full load, 0.8 pf, is:

Hint
Q48). The fraction of full load at maximum efficiency is:

Hint
Q49). Transformers are rated in kVA rather than kW because:

Hint
Q50). A transformer reaches a maximum efficiency of 98.5% at unity pf when delivering 80 kVA. Its iron loss is about:

Hint

Transformer Calculations MCQs for Interviews

Q51). A 25 kVA transformer has Pi = 250 W and Pcu(fl) = 400 W. At 60% load and 0.8 pf, the efficiency is:

Hint
Q52). A 200 kVA transformer has Pi = 1.0 kW and Pcu(fl) = 2.0 kW. Its maximum efficiency at 0.9 pf is:

Hint
Q53). The voltage regulation of a transformer, referred to the no-load voltage (the convention used in this bank), is defined as:

Hint
Q54). The no-load secondary voltage is 240 V and the full-load secondary voltage is 230 V. Taking regulation as the voltage fall as a percentage of the no-load voltage, the regulation is:

Hint
Q55). The regulation at full load, 0.8 pf lagging, is:

Hint
Q56). The regulation at full load, unity pf, is:

Hint
Q57). The regulation at full load, 0.8 pf leading, is

Hint
Q58). The load power factor at which the regulation is maximum is:

Hint
Q59). The maximum regulation is:

Hint
Q60). The power factor at which the regulation is zero is:

Hint
Q61). A transformer has R = 0.02 pu and X = 0.05 pu. At full load, 0.8 pf lagging, the regulation is:

Hint

Before attempting transformer numerical problems, it is important to understand the basic concepts of transformers. You can strengthen your fundamentals by practising our 100+ Transformer MCQs with Answers, covering transformer principles, types, construction, testing, applications and other important theoretical concepts.

Q62). The percentage resistance and reactance drops ε_r and ε_x are:

Hint
Q63). The full-load regulation at 0.8 pf lagging is:

Hint
Q64). The secondary terminal voltage at full load, 0.8 pf lagging, with 2000 V applied, is:

Hint
Q65). A transformer has a full-load regulation of 3.6% at 0.8 pf lagging. At half load (same pf), the regulation is approximately:

Hint
Q66). A transformer has a 5% regulation (referred to the no-load voltage) and a no-load secondary voltage of 400 V. The loaded secondary voltage is:

Hint
Q67). A transformer has a per-unit impedance of 5%. The steady-state short-circuit current, with rated voltage applied, is how many times the rated current?

Hint
Q68). A 1000 kVA, 11 kV/433 V, 3-phase transformer has 5% impedance. The short-circuit current on the LV side, with rated voltage on the HV side, is about:

Hint
Q69). A transformer has ε_r = 2% and ε_x = 6%. At 0.6 pf lagging the regulation is:

Hint
Q70). A transformer supplies a load with a leading power factor lower than its zero-regulation power factor (that is, a more capacitive load). The secondary terminal voltage:

Hint
Q71). Which of the following is NOT required for two transformers to operate in parallel with proportional load sharing

Hint
Q72). Two transformers of 100 kVA and 200 kVA have equal percentage impedance. They supply a total load of 240 kVA. The shares are:

Hint
Q73). The load on T1 is:

Hint
Q74). The load on T2 is:

Hint
Q75). Which transformer is overloaded in this case?

Hint

Transformer Calculations MCQs for Quiz

Q76). The maximum total load that can be supplied without overloading either transformer is:

Hint
Q77). A 500 kVA, 5% transformer is paralleled with a 250 kVA, 4% transformer. The maximum load without overloading either is:

Hint
Q78). A 100 kVA, 4% transformer is in parallel with a 150 kVA, 3% transformer. The maximum total load is:

Hint
Q79). For the same pair as Q78, with a total load of 200 kVA, the 150 kVA transformer carries:

Hint
Q80). Two 400 kVA transformers have impedances of 5% and 6%. They supply 600 kVA. The first (5%) carries:

Hint
Q81). If two transformers in parallel have different voltage ratios, then:

Hint
Q82). Two transformers in parallel have secondary EMFs differing by 2 V. The sum of their impedances referred to the secondary is 0.2 Ω. The no-load circulating current is:

Hint
Q83). Two transformers of equal kVA rating, each with 4% impedance, have voltage ratios that differ by 1%. The circulating current as a percentage of rated current is:

Hint
Q84). Two transformers have equivalent impedances of |Z1| = 0.5 Ω and |Z2| = 1.0 Ω with the same impedance angle. The total load current is 300 A. The current in the first transformer is:

Hint
Q85). Two transformers of 300 kVA and 700 kVA have equal per-unit impedance. The total load is 600 kVA. The 700 kVA unit carries:

Hint
Q86). Two 500 kVA transformers have impedances of 2% and 4%. The total load is 600 kVA. The load on the 4% transformer is:

Hint
Q87). A Dyn11 transformer and a Dyn1 transformer of the same ratings:

Hint
Q88). Yy0 and Dd0 transformers of equal ratio and impedance:

Hint
Q89). Connecting transformers in parallel with the wrong phase sequence causes:

Hint
Q90). If paralleled transformers have different X/R ratios, then:

Hint
91). As a rule of thumb, paralleling transformers whose kVA ratings differ by more than about 3:1 is generally avoided because:

Hint
Q92). A 200 kVA transformer has 2.5% impedance. On a 100 kVA base, with the voltage base unchanged, its per-unit impedance is:

Hint
Q93). A transformer has X1 = 5 Ω, X2 = 0.03 Ω and K = N2/N1 = 0.1. The equivalent reactance referred to the primary, X01, is:

Hint
Q94). A 1000 kVA transformer with 6% impedance is supplied from an infinite bus. The fault level on its secondary side is:

Hint
Q95). A 500 kVA transformer has 5% impedance. On a 1000 kVA base, with the voltage base unchanged, it is:

Hint
Q96). A 440 V/220 V autotransformer delivers 10 kVA to the load. The power transferred by transformer action (not by direct conduction) is:

Hint
Q97). Compared with a two-winding transformer of the same output, the saving in copper for an autotransformer with k = 0.5 is about:

Hint
Q98). The Sumpner (back-to-back) test on two identical transformers is used to determine:

Hint
Q99). A 3-phase, 500 kVA, 11 kV/415 V transformer has an LV line current of:

Hint
Q100). The cooling designation ONAN stands for:

Hint

Working through these 100 questions should have made a few patterns clear. Losses decide almost everything else. Iron loss is fixed by voltage and frequency, copper loss grows with the square of the load, and the efficiency, the ideal operating point and the heating all follow from those two facts. Efficiency peaks where the two losses are equal. This is why distribution transformers, which are always energised but often lightly loaded, are designed differently from those that run near full load.
Regulation depends on power factor as much as on load. Lagging loads make the terminal voltage fall. Sufficiently leading loads can make it rise. Between them lies a power factor at which regulation is zero.
In parallel operation, per-unit impedance matters more than kVA rating. A transformer with lower per-unit impedance takes more than its share of the load and reaches its limit first. That can leave the pair unable to supply the sum of their ratings.
If you got a question wrong, redo it from its hint before moving on. A mistake in a hint or a worked answer is also worth checking against your textbook. Doing this a few times usually makes the formulas automatic, and that is the real goal of any practice set.

clock.png

Time's up

SEARCH HERE!

Recent Posts

  • Synchroscope : Construction, Working, Types, Advantages, Disadvantages & Its Applications
  • Electromagnetic Relay : Construction, Working, Circuit, Types & Its Applications
  • Seebeck Effect : Formula, Differences, Coefficients, Example, Advantages & Its Applications
  • Flow Switch : Construction, Working, Circuit, Types & Its Applications
  • Shaded Pole Motor : Construction, Working, Circuit, Characteristics & Its Applications
  • Induction Generator : Construction, Working, Circuit, Types, Differences & Its Applications
  • Squirrel Cage Induction Motor : Construction, Working, Types, Differences & Its Applications
  • Proximity Effect : Working, Affecting Factors, Differences, Advantages, Disadvantages & Its Applications
  • Solid State Relay : Block Diagram, Circuit, Working, Types, Differences & Its Applications
  • Cycloconverter : Circuit, Working, Types, Control Strategies, Characteristics & Its Applications

Categories

  • Basics
  • Electrical
  • Electrical Circuits
  • Electrical Machines
  • Electrical Measurements
  • Electrical Projects
  • Electromagnetic Fields
  • Power Electronics
  • Power Plant
  • Power Systems

Copyright © 2026 · WatElectrical.com | Contact Us | Privacy Policy